Chemical injection
Dosing packages for methanol, acids, inhibitors, diluent and water.

The right dose, every time.
- Dosing matched to your process flow
- Pumps, tank and controls on one skid
- Multiple pumps and chemicals possible
- Designed to ASTM, ASME, ISO and API standards
A selection of chemical injection skids we have built
Real projects, photographed in our workshops and at site. Ask us for references in your application.




- Methanol injection skidPDVSA
- Chemical and methanol injection packagesConocoPhillips
- Diluent injection and surge relief skids, José terminalAmeriven / Vepica
- Sulfuric acid injection skidBauxilum
- Chlorine dosing skidWater treatment
How it works, configurations and standards
Open the sections you need. Everything stays on the page for reference and print.
01How it works
Process diagram and step-by-step timeline
Chemical injection skids deliver the chemical your process needs, at the rate the process calls for. We have built packages for methanol, sulfuric acid, water and diluent injection, and chlorine dosing.
We select pumps, tank and controls for your chemical, flow and pressure, and assemble everything on one skid.
Dosing skids are used in oil and gas, chemical, petrochemical, food processing, mining, pharmaceutical, pulp and paper, cement and water treatment facilities to inject or dose a precise amount of chemical, diluent or lubricant. The aim is the right dose: under or over dosing can damage the process.
Example, chlorine dosing package for a potable water tank. Main components: chemical storage tank, positive displacement pumps with electric solenoid drive, pulsation damper for each pump, calibration column, ultrasonic level transmitter, rotameter flow sensor and transmitter, control panel and PVC interconnecting piping. Scope: detailed engineering, materials procurement, manufacture, equipment assembly, electrical and instrumentation work, tightness test and FAT. Deliverables: general arrangement drawings, structural frame and supports drawings, lifting analysis, control panel diagrams, piping arrangement drawings, FAT protocol, operation and maintenance manual and Data Book.
In the order the fluid passes through it. Select a step, use the arrows, or let it play.
Typical schematic configuration, shown for reference only. The final design, equipment, instrumentation and applicable codes depend on the client's process conditions, specification and project requirements, and are defined during engineering.
Swipe sideways to see the whole diagram.
Chemical storage
A tank sized for your consumption, with vent, fill and drain connections and a level instrument.
Suction
An isolation valve and a strainer protect the pumps from debris. A low tank outlet keeps the pump suction flooded. A calibration column on the suction lets pump output be checked against a measured volume.
Dosing pumps
Metering pumps deliver the set dose. Duty and standby pumps, or one pump per chemical or injection point.
Pulsation damping
A pulsation damper smooths the pump pulses, for steadier flow and calmer piping.
Pressure protection
A relief valve returns flow to the tank if pressure rises. A back-pressure valve keeps discharge pressure steady.
Flow verification
A check valve prevents backflow. A flow indicator confirms the dose delivered.
Injection point
An injection quill places the chemical in the process line, with a check valve and an isolation valve.
Control
Sets the dose from the process flow, runs the pumps, alarms on low level or pressure and reports to your SCADA.
02Typical configurations and options
What goes on the skid and what can change
- ServiceMethanol, sulfuric acid, water, diluent, chlorine; inhibitors and other chemicals per project
- Storage tankSized for your consumption; cylindrical or rectangular, horizontal or vertical; carbon steel, stainless steel or plastic; vent, fill and drain
- Dosing pumpsDiaphragm or plunger metering pumps; duty and standby, or several pumps
- Dose controlManual stroke or speed, or automatic ratio to the process flow
- Pulsation dampingPulsation damper on the pump discharge, where needed
- Pressure protectionRelief valve with return to the tank; back-pressure valve
- VerificationCalibration column, flow indicator or flow meter
- Injection pointInjection quill or nozzle with check and isolation valves
- Level and alarmsLevel gauge or transmitter; low-level and pressure alarms
- Control panelLocal panel or PLC; serial and Ethernet to your SCADA
- Area classificationInstruments, panels and wiring selected for the classified area
- ContainmentDrip tray or bunded base under the skid, as required
- ComponentsWe integrate Milton Roy and Pulsafeeder pumps, Swagelok, Yokogawa, Flowserve and Magnetrol, and consider your preference
03Standards and documentation
Design references and the documents we deliver
Designed to ASTM, ASME, ISO and API standards. The applicable codes are agreed per project.
Typical references
- API 675Controlled-volume metering pumps, where specified
- API 674Reciprocating positive displacement pumps
- ASME B31.3Process piping
- ASME VIII Div. 1Pressure vessels, such as pulsation dampers
- API 520 / 521Pressure-relieving devices and systems
- NACE MR0175 / ISO 15156Materials for sour (H2S) service
Typical documentation package
- P&ID
- General arrangement
- Instrument and pump datasheets
- Calculations
- FAT procedure and report
- Operation and maintenance manual
Factory acceptance test (FAT) in our workshops and site acceptance test (SAT) at the installation site.
Typical brands on this skid
Brands we represent, integrated alongside your preference.




One team, from engineering to the factory test
- Step 1
Engineering
Process, mechanical and instrumentation design from your specification.
- Step 2
Fabrication
Built and assembled in our workshops to the agreed codes.
- Step 3
Factory test (FAT)
Loop-by-loop checks, valve stroking and control verification, with your witnesses if you wish.
- Step 4
Start-up
Documentation, delivery and remote support.